Part identity
04770030 004
Circuit Breaker
Honeywell Control Systems Ltd
Avg quote: 14 minFulfilled from Anaheim, CAAS9120:2025 · ISO 9001 · FAA AC 00-56BC of C, lot & date code with every line
Part description
Circuit Breaker
ASAP supports this specific part for replacement, spare-pool replenishment, retrofit, and urgent maintenance requirements. Quote requests can include alternate MPN, condition preferences, certification needs, and plant-specific receiving instructions so procurement gets a clear sourcing response before purchase.
Specifications
Certifications & documentation
- UL Recognized
- CE
- C of C available on request
HC
Manufacturer
Honeywell Control Systems Ltd
Authorized-distributor or qualified-aftermarket source. Parts shipped from this manufacturer include full traceability paperwork and counterfeit-mitigation per SAE AS6081.
View manufacturer profile →NSN Information for Part Number 04770030 004 with NSN 5925-00-581-0393, 5925005810393
Characteristics Data of NSN 5925-00-581-0393, 5925005810393
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 4.750 INCHES NOMINAL |
| ADAT | BODY WIDTH | 1.030 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 2.830 INCHES NOMINAL |
| ADTV | CASE MATERIAL | PLASTIC |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.380 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 100.500 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| PKWT | UNPACKAGED UNIT WEIGHT | 0.688 POUNDS |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 BUS BAR |