Item Name: circuitbreaker | NSN: 5925-00-755-2880 (5925007552880) | CAGE Code: 98437 |
FSC: 5925 Circuit Breakers |
If you require part number DS5-1-2B from Ellis And Watts International Llc which is described as a Circuitbreaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number DS5-1-2B which is listed under the Federal Supply Class 5925 Circuit Breakers. To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925007552880 and was produced under the CAGE Code 98437. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part DS5-1-2B today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-755-2880 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007552880 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
DS5-1-2B | 1 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC AND 10.0 AMPERES DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC AND 2000.0 DC SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT AND 3.000 MINIMUM AT 400 PCT AND 11.000 MAXIMUM AT 400 PCT SINGLE LOCATION |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC AND 30.0 AC AND 30.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL |
CPRW | ACTUATOR FUNCTION | RESET |
CQJX | NOMINAL THREAD SIZE | 0.469 INCHES |
TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |