| Part No. : WC375 01-011 | Alternate P/N : WC37501011 | Manufacturer : federal specifications |
| Item Name: circuit breaker | NSN: 5925-00-782-6845 (5925007826845) | CAGE Code: 81348 |
If you require part number WC375 01-011 from Federal Specifications which is described as a Circuit Breaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number WC375 01-011 which is listed under the Federal Supply Class . To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925007826845 and was produced under the CAGE Code 81348. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part WC375 01-011 today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-782-6845 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007826845 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | U | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| Q0170 | 5 | 1 | C | A |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAT | BODY WIDTH | 0.720 INCHES MINIMUM AND 0.740 INCHES MAXIMUM |
| AJEC | BOSS HEIGHT | 0.240 INCHES MINIMUM AND 0.260 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| TTQY | TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 COMPRESSION |
| ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/1 GOVERNMENT SPECIFICATION |
| ADAQ | BODY LENGTH | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
| ADAU | BODY HEIGHT | 2.570 INCHES MINIMUM AND 2.590 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 120.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TEST | TEST DATA DOCUMENT | 81348-W-C-375 SPECIFICATION INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTING G |
If you have more than one item, you can also send us your part number list (Spreadsheet) by uploading your list here.