Part No. : ED63A040 | Manufacturer : siemens energy and automation inc | Item Name: circuit breaker |
NSN: 5925-01-343-3595 (5925013433595) | CAGE Code: 66842 | FSC: 5925 Circuit Breakers |
If you require part number ED63A040 from Siemens Energy And Automation Inc which is described as a Circuit Breaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number ED63A040 which is listed under the Federal Supply Class 5925 Circuit Breakers. To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925013433595 and was produced under the CAGE Code 66842. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part ED63A040 today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs. ED63A040
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-343-3595 Item Description: Circuit Breaker | 5925 | 013433595 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Ed63a040 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | ||
ABHP | OVERALL LENGTH | 6.344 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 3.000 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.406 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.219 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS AND 30000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +115.0/+375.0 AC ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AKPX | POLE QUANTITY | 3 |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
If you have more than one item, you can also send us your part number list (Spreadsheet) by uploading your list here.
Upload