| Part No. : 5682D19G21 | Manufacturer : westinghouse science and technology | Item Name: circuit breaker |
| NSN: 5925-00-828-0708 (5925008280708) | CAGE Code: 01269 |
If you require part number 5682D19G21 from Westinghouse Science And Technology which is described as a Circuit Breaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number 5682D19G21 which is listed under the Federal Supply Class . To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925008280708 and was produced under the CAGE Code 01269. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part 5682D19G21 today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-828-0708 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008280708 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | U | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| QCC3150Y | 2 | 9 | 5 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 3.563 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.562 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| ADAQ | BODY LENGTH | 6.500 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.562 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 50.000 MINIMUM AT 200 PCT AND 200.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CTJS | UNPACKAGED UNIT WEIGHT | 4.000 POUNDS NOMINAL |
If you have more than one item, you can also send us your part number list (Spreadsheet) by uploading your list here.